MULTIBOX 160A  Multibox 160A, DIN 00

Series: MULTIBOX 160A

Multibox 160A, DIN 00

Free Sample Request

4 Variants


Description

  • Glass fiber Polyester
  • Difficult to burn
  • Impact resistant

Unique Selling Proposition

  • Modern, practical design
  • On request flush-mounted cover with stainless steel plate
  • Thanks to only 117mm installation depth and insulation material, the insulated building envelope is not weakened when installed in flush-mounting
  • Suitable for minergie standard

Characteristics

  • With 3 x 1-pole fuse switch disconnector
  • Bolt lock (4-kant with Slot)
  • Protection 2-piece, transparent and sealable
  • N-connector for TN-C to TN-S
  • N-connector separating Piece self-opening when loosening the screw
  • Voltage test possible only if fuse with not insulated straps used
  • Combintion possible
  • Mounting type surface / flush

Whether surface or flush-mounted, with Multibox you always work with the same housings and fuse elements (60A) or switch-disconnectors (DIN00). The additional housings, which can be attached with one click, give you maximum flexibility with a minimum of effort. (1)

[Swipe to the left and right for more options]

Rated Current Ie

160 A  @  500 VAC

125 A@  690 VAC

Rated voltage Ue

690 VAC

Rated isolation voltage Ui

1000 VAC

Rated Power Operating Frequency fe

50 Hz

NH-Fuse-Links with screw terminal for cable lug

M8 

Fuse Element with double terminals strap

6  -  70 mm²

Fuse-Link

DIN 00 

Rated Current Ie

160 A  @  500 VAC

125 A@  690 VAC

Rated voltage Ue

690 VAC

220 VDC

Rated isolation voltage Ui

1000 VAC

Rated Power Operating Frequency fe

50 Hz

Rated Impulse Withstand Voltage Uimp

8 kV

Conditioned Rated Short Cicuit Current

80 kA␠ @  500 VAC

50 kA␠ @  690 VAC

␠ 

Rated Impulse Withstand Voltage Uimp

8 kV

Conditioned Rated Short Cicuit Current

50 kA  @  500 VAC

Rated short-time withstand current with fuse links

20 kA␠ @  500 VAC

Allowed Ambient Temperature

-25 °C to +40 °C acc. to IEC 61439

Protection by closed housing

IP54

Neutral Disconnector with Straps

6   - 70 mm²

Earth Connection Bride

6  -  70 mm²

Double erminal

6  -  50 mm²

Earth Connection (outside)

M8 

Category of use AC

AC-23B  @  400 VAC

AC-22B  @  500 VAC

AC-21B  @  690 VAC

Category of use DC

DC-22B  @  220 VDC

Rated power dissipation with-out NH fuse-links at Ith

2.3 W

Protection class

IP20 

Mechanical lifetime

1400  Insertions​

Electrical lifetime

200  Insertions​

Ambient Temperature Tu**)

-40 °C to +55 °C

**) A reduction of the rated current is required above 30°C

Detailed information on product approvals, code requirements, usage instructions and detailed test conditions can be looked up in   Details about Approvals


Approvals

The approval mark is used by the testing authorities to certify compliance with the safety requirements placed on electronic products.


Approval Reference Type: Multibox

Approval Logo Certificates Certification Body Description


Compliances

The product complies with following Guide Lines

Identification Details Initiator Description
Approval marks CE SCHURTER AG The CE marking declares that the product complies with the applicable requirements laid down in the harmonisation of Community legislation on its affixing in accordance with EU Regulation 765/2008.
Approval marks Zulassung_Symbol_UKCA SCHURTER AG The UKCA marking declares that the product complies with the applicable requirements laid down in the British Amendment of Regulation (EC) 765/2008.
Environment_Safety REACH SCHURTER AG On 1 June 2007, Regulation (EC) No 1907/2006 on the Registration, Evaluation, Authorization and Restriction of Chemicals 1 (abbreviated as "REACH") entered into force.

900150090000005551
LOADING...

Assembly Instructions

1. Cover Plate 2-piece, transparent and lockeable
2. NH-NH fuse load-•breaker
3. Hinged window
4. Inner Cover
5. Various connection variants•clamp•Cable lug•Double terminals
6. Square lock
7. Neutral conductor isolator for TN-S/TN-C
8. Labeling field
9. External ground connection (optional)
10. Cable fixing (optional)
11. Front frame for UP mounting
12. 63A- Fuse element with different connection variants

Diagrams

TN-S (delivered condition)

L = Pole conductor
PE = Protective conductorPEN = PEN conductor
N = Neutral conductor
NE = Neutral earth conductor
TS = Separating screw
KA = Cable armor
TN-C

L = Pole conductor
PE = Protective conductorPEN = PEN conductor
N = Neutral conductor
NE = Neutral earth conductor
TS = Separating screw
KA = Cable armor


Short Table of Variants MULTIBOX 160A Open complete table MULTIBOX 160A

Designation Terminal Order Number
E-No. Free Sample

Free Sample


Please ask for free sample in order to check if the products meets your requirement for your application.
Send your delivery adress and your specific requirements.

Distributor Stock Check

Distributor Stock Check


The following links refers to the inquiry form for distributors stock information of the selected products. It allows checking for the available amount and optionally to place an order at your selected partner.
The stock availability at the distributors may also be called up separately and the desired product manually entered.
Stock Check Distributor

...
 
MULTIBOX AP HAK 160A DIN00+0+E Straps 0009.5165 131DDAA¹⁾ ...
MULTIBOX AP HAK 160A DW DIN00+0+E Double Terminal 0009.5167 161DGAA¹⁾ ...
MULTIBOX UP HAK 160A DIN00+0 Straps 0009.5166 331QQBA¹⁾ ...
MULTIBOX UP HAK 160A DW DIN00+0 Double Terminal 0009.5168 361QQBA¹⁾ ...

¹⁾ E-Nr. corrisponde to ordercode

Packaging unit 1 Pcs 

900150090000005551
LOADING...
Alternative: Direct installation in concrete or other rated current (3)

[Swipe to the left and right for more options]


19.11.2024
   